R4140GFlame Safeguard Programming ControlsPRODUCT DATAAPPLICATIONThe R4140G Flame Safeguard Programmers provideflameout protection plus automatic sequencing of the burnermotor (blower), firing rate motor, ignition, pilot valve, and mainfuel valve(s) for commercial and industrial burners using gas,oil, coal, or a combination of fuels.FEATURES• Approvals: Underwriters Laboratories Inc. listed orcomponent recognized, Canadian StandardsAssociation certified, and Factory Mutual approved forautomati

Содержание резюме на странице нет 2

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSInterlock Circuits:Start Interlocks (R4140G1049, G1056, G1064, G1114,G1122, G1148 and G1171)—System controls must bein proper positions or programmer will not start.Preignition Interlocks (R4140G1007, G1015, andG1106)—Must be closed to start programmer. Preventignition trials if interlocks open during prepurge; timerrecycles the programmer and system restarts ifcondition is self-correcting.Running Interlocks (all models)—Must be closed (airflowmus

Содержание резюме на странице нет 3

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSSafety Features:Safe Start Check—For the presence of a flame (or acondition simulating a flame) provided at startup andduring prepurge. If the flame relay 2K is pulled in atstartup, 2K2 is open and the programmer cannot bestarted. If the flame relay 2K pulls in during prepurge(before 57.5 seconds), 2K2 opens, relay 1K drops out,and ignition trials cannot be started. Instead, the timercompletes its revolution and stops at the standby position(zero seco

Содержание резюме на странице нет 4

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSLOCKOUT SWITCHRESET BUTTON2-11/32 (60)2-3/8 (60)47/64(19)35/64(14)202050C COVER1-51/64(46)7/8 (22) DIAMETER KNOCKOUT (2)2-5/64(53)3/8 (10) (4)13/64 (5) DIAMETER (4)(FOR MOUNTING ON4 X 4 [102 X 102] JUNCTION BOX)5/8 (16) (4)6-1/2(165)33-3/8(86)6-5/32(156)54L11869L21771012168111315GF147-3/16 (183)202050C COVER1-3/4(45)15/16(24) (2)6(152)7/8 (22) DIAMETERKNOCKOUT (2)31/32(25) (2)1-27/32(47)15-7/8(149)3-3/8 (86)7 -1/16 (179)5-5/8(143)7-3/16 (183)31/32(25)1-

Содержание резюме на странице нет 5

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSR1298020 Cable; for flame detector (F lead-wire)installations in a high temperature environment; ratedup to 400°F (204°C) for continuous duty; tested foroperation up to 600V and breakdown up to 7500V.R1239001 High Tension Ignition Cable; for ignitioninstallations in a contaminating environment; veryresistant to severe conditions of oil, heat, and corona,and tested to withstand high voltages up to25,000V rms in a salt bath for one minute withoutbreakdo

Содержание резюме на странице нет 6

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSOPERATIONModels with Preignition Interlocksto each timer contact. Refer to Fig. 4 and the Step-by-StepOperation section.Fig. 3 shows all contacts in the standby position (zeroseconds). The opening and closing times are shown adjacentR4140G1007/G1015 SCHEMATIC(WITH/WITHOUT HEAVY DUTY COVER)INTERNAL120V, 60 HZPOWER SUPPLYL2L1(HOT)1EXTERNALUNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.A TIMER CONTACTS SNAP CLOSED.B CONTACTS SNAP OPEN.O—OPENING TIMEC

Содержание резюме на странице нет 7

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSTIMER 0SECONDS1020304050607080901001106PREIGNITION INTERLOCKSRUN 5PERIODRUNNING INTERLOCKS (PROVEN AIRFLOW)BURNERMOTOR(BLOWER)INTERRUPTEDPILOT/IGNITIONMAIN FUELVALVE(S)(GAS OR OIL)8PURGE51510 SECONDS630 SECONDS7HIGH FIRE POSITIONFIRING RATEMOTORSWITCHINGSTOPSTOPSTOP3STARTSTARTTIMERMOTORMAINIGNPILOTPREPURGESTARTTIMER DIAL12010 TO 11MODULATELOW FIRE POSITION1LOW12 TO 11LOW14 TO 112222ACTUALDAMPEROPERATION4MOTORDRIVESDAMPERCLOSEDMOTORDRIVESDAMPEROPEN31TERM

Содержание резюме на странице нет 8

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSIgnition Trials60 seconds—M4A closes; power is applied to terminals 5and 6, energizing the ignition transformer and pilotvalve (or main fuel valve(s) on terminal 7 if using directspark ignition).— When a flame is detected, relay 2K pulls in, 2K2opens, and the LS HTR stops heating; 2K1 and2K3 close.66 seconds—M3A closes, bypassing the low fire switchand the timer switch.70 seconds—M2B opens; pilot or ignition trial ends; aflame must be detected b

Содержание резюме на странице нет 9

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS120V, 60 HZPOWER SUPPLYL2L1(HOT)1R4140G1106 SCHEMATICINTERNALEXTERNALUNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.A TIMER CONTACTS SNAP CLOSED.B CONTACTS SNAP OPEN.O—OPENING TIMEC—CLOSING TIMELS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER1MASTERSWITCHL2L12334G9135812NUMBERS BELOWDESIGNATE LINELOCATIONSRELAY CONTACTS.(UNDERLINEINDICATES ANORMALLY CLOSEDCONTACT.)10FLAME SIGNALMETER JACKFPLUG-IN AMPLIFIER5FLAMEDETECTOR671771781110M7AC-57.5 O-111BURN

Содержание резюме на странице нет 10

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSTIMER 0SECONDS1020304050607080901001106PREIGNITION INTERLOCKSRUNPERIODRUNNING INTERLOCKS (PROVEN AIRFLOW)BURNERMOTOR(BLOWER)INTERRUPTEDPILOT/IGNITIONMAIN FUELVALVE(S)(GAS OR OIL)8PURGE51510 SECONDS615 SECONDS7HIGH FIRE POSITIONFIRING RATEMOTORSWITCHINGSTOPSTOPSTOP3STARTSTARTTIMERMOTORMAINIGNPILOTPREPURGESTARTTIMER DIAL12010 TO 11MODULATELOW FIRE POSITION1LOW12 TO 11LOW14 TO 112222ACTUALDAMPEROPERATION4MOTORDRIVESDAMPERCLOSEDMOTORDRIVESDAMPEROPEN31TERMIN

Содержание резюме на странице нет 11

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSIgnition Trials60 seconds—M4A closes; power is applied to terminals 5and 6, energizing the ignition transformer and pilotvalve (or main fuel valve(s) on terminal 7 If using directspark ignition).— When a flame is detected, relay 2K pulls in, 2K2opens, and the LS HTR stops heating; 2K1 and2K3 close.66 seconds—M3A closes, bypassing the low fire switchand the timer switch.70 seconds—M2B opens; pilot or ignition trial ends; aflame must be detected b

Содержание резюме на странице нет 12

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS120V, 60 HZPOWER SUPPLYL2L1(HOT)1R4140G1049 SCHEMATIC(WITH/WITHOUT HEAVY DUTY COVER)INTERNALEXTERNALUNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.A TIMER CONTACTS SNAP CLOSED.B CONTACTS SNAP OPEN.O—OPENING TIMEC—CLOSING TIMELS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATERMASTERSWITCHL11L22334G9135812NUMBERS BELOWDESIGNATE LINELOCATIONS OFRELAY CONTACTS.(UNDERLINEINDICATES ANORMALLY CLOSEDCONTACT.)10FLAME SIGNALMETER JACKFPLUG-IN AMPLIFIER5FLAMEDETEC

Содержание резюме на странице нет 13

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSTIMER 0SECONDS1020304050607080901001106RUN 5PERIODRUNNING INTERLOCKS (PROVEN AIRFLOW)IGNBURNERMOTOR(BLOWER)5 SECONDIGNITIONINTERRUPTEDPILOT/IGNITIONMAIN FUELVALVE(S)(GAS OR OIL)PURGE5118510 SECONDS630 SECONDS7HIGH FIRE POSITIONFIRING RATEMOTORSWITCHINGSTOPSTOPSTOPSTART38MAINPILOTSTARTTIMERMOTORPREPURGESTARTTIMER DIAL12010 TO 11MODULATELOW FIRE POSITION1LOW12 TO 11LOW14 TO 112222ACTUALDAMPEROPERATION4MOTORDRIVESDAMPERCLOSEDMOTORDRIVESDAMPEROPEN31TERMINAL

Содержание резюме на странице нет 14

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSIgnition Trials60 seconds—M4A closes; power is applied to terminals18, 5, and 6, energizing the ignition transformer andpilot valve (or main fuel valve(s) on terminal 7 if usingdirect spark ignition).— When a flame is detected, relay 2K pulls in, 2K2opens, and the LS HTR stops heating; 2K1 and2K3 close.65 seconds—M9B opens; 5 second ignition (terminal 18)is de-energizes (pilot only until 70 seconds).66 seconds—M3A closes, bypassing the low fire

Содержание резюме на странице нет 15

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS120V, 60 HZPOWER SUPPLYL2L1(HOT)1R4140G1056/G1064 SCHEMATIC(WITH/WITHOUT HEAVY DUTY COVER)INTERNALEXTERNALUNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.A TIMER CONTACTS SNAP CLOSED.B CONTACTS SNAP OPEN.O—OPENING TIMEC—CLOSING TIMELS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATERMASTERSWITCHL11L22334G9135812NUMBERS BELOWDESIGNATE LINELOCATIONS OFRELAY CONTACTS.(UNDERLINEINDICATES ANORMALLY CLOSEDCONTACT.)10FLAME SIGNALMETER JACKFPLUG-IN AMPLIFIER5FLAM

Содержание резюме на странице нет 16

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSTIMER 0SECONDS1020304050607080901001106RUN 5PERIODRUNNING INTERLOCKS (PROVEN AIRFLOW)IGN85 SECONDIGNITION1810 SECONDINTERRUPTEDPILOT/IGNITION5INTERMITTENT PILOTOR 1ST STAGEFUEL VALVE6MAIN FUELVALVE(S)(GAS OR OIL)7PURGE51HIGH FIRE POSITIONFIRING RATEMOTORSWITCHINGSTOPSTOPSTOPSTART3BURNERMOTOR(BLOWER)MAINPILOTSTARTTIMERMOTORPREPURGESTARTTIMER DIAL12010 TO 11MODULATELOW FIRE POSITION1LOW12 TO 11LOW14 TO 112222ACTUALDAMPEROPERATION4MOTORDRIVESDAMPEROPENMOTO

Содержание резюме на странице нет 17

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSIgnition Trials60 seconds—M4A closes; power is applied to terminals18, 5, and 6, energizing the ignition transformer andpilot valve (or first stage fuel valve when using directspark ignition).— When a flame is detected, relay 2K pulls in, 2K2opens, and the LS HTR stops heating; 2K1 and2K3 close.65 seconds—M9B opens; 5 second ignition (terminal 18)de-energizes (pilot only until 70 seconds).66 seconds—M3A closes, bypassing the low fire switchand t

Содержание резюме на странице нет 18

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS120V, 60 HZPOWER SUPPLYL2L1(HOT)1INTERNALEXTERNALUNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.A TIMER CONTACTS SNAP CLOSED.B CONTACTS SNAP OPEN.O—OPENING TIMEC—CLOSING TIMELS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER1MASTERSWITCHL1L22334G95812FLAME SIGNALMETER JACKPLUG-IN AMPLIFIERFLAMEDETECTOR617717TIP JACK8LIMITSBURNERCONTROLLER 3102M11BC-15 O-7071616M7AC-67 O-168TOTERMINAL82K3412112KSTARTINTERLOCK(S) 41K - 12, 17, 17LS - 8, 22,2K2LS HTR3RUNN

Содержание резюме на странице нет 19

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLSTIMER 0SECONDS1020304050607080901001101201301401501601701806RUNNING INTERLOCKS (PROVEN AIRFLOW)110 SECONDS5INTERRUPTEDPILOT/INGITION630 SECONDS (WITHOUT JUMPER)60 SECONDS (WITH JUMPER)6MAIN FUELVALVE(S)(GAS OR OIL)STOP185STOP5 SECONDINGITION3START8STOPSTARTBURNERMOTOR(BLOWER)PURGEPILOTSTARTTIMER MOTORMAINIGNPREPURGETIMER DIAL7HIGH FIRE POSITION10 TO 11MODULATELOW FIRE POSITION1LOW12 TO 11LOW14 TO 11222ACTUALDAMPEROPERATIONMOTORDRIVESDAMPEROPEN324MOTORDR

Содержание резюме на странице нет 20

R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS148 seconds—M8A closes, M8B opens; firing rate motor isreleased to modulate under control of the Series 90Controller.155 seconds—M5B opens; timer stops with the system inthe Run condition.Ignition Trials70 seconds—M4A closes; power is applied to terminals18, 5 and 6, energizing the ignition transformer andpilot valve (and terminal 7, main oil valve solenoid, ifusing direct spark ignition of oil).— When flame is detected, relay 2K pulls in, 2K2op